The new Mycond heat pump model offers high technical performance and efficiency, running on environmentally friendly R290 Freon. It provides efficient heating even at -25 degrees, reaching temperatures of up to +75 degrees
Cooling capacity: 32-64,4 kW
Heating capacity: 50-90 kW

Want to buy or have questions?
Modular heat pump series Propane MCU-YHP

Expansion to 16 modules allows flexibility and energy optimization, and the compact housing guarantees quality and reliability.

Environmentally conscious choice

Air-source heating

High reliability:

  • Multi-level protection
  • Alternating operating/defrosting cycle
  • Corrosion protection

Eco-friendly:

  • R290 refrigerant, low GWP (GWP = 3)
  • Reduced carbon emissions

Easy to use:

  • Intelligent climate curves automatically adjust the water temperature
  • Higher outlet water temperature up to 75°C

Fully inverter:

  • High efficiency for energy savings
  • Fast start-up and reduced start/stop frequency

EVI (Enhanced Vapour Injection):

  • With EVI, the unit can operate at ambient temperatures as low as -25°C.

Comfort:

  • Multiple quite operating modes
Specifications Units MCU050YHP MCU075YHP
Heating capacity range kW 17,56~50 20.24~91.59
Heating (A7/W35)      
Heating capacity kW 50,00 90
Capacity kW 12,35 21.5
COP W/W 4,05 4.18
Heating (A7/W55)      
Heating capacity kW 50,00 91.6
Capacity kW 17,50 29.4
COP W/W 2,86 3.12
Cooling (A35/W7)      
Cooling capacity kW 32,00 64,5
Capacity kW 13,30 21,98
EER W/W 2,41 2,93
Low-temperature mode (W35)   A++ A+++
Medium-temperature mode (W55)   A++ A+++
SCOP (35°C)   3,8 4.86
SCOP (55°C)   3,32 3.87
Rated water flow m3/h 8,60 12.9
Fan      
Compressor   DC inverter DC inverter
Freon   R290 R290
Sound pressure level dB(A) 60 65
Rated voltage /Frequency V/F/Hz 400/3N~/50 380~415/3/50
Maximum input power kW 19,84 45.84
Maximum input current  А 30,30 70.6
Dimensions L/W/H mm 1155/990/1880 2200/1100/2190
Weight kg 500 770

Notes:

1. Cooling capacity and electrical power consumption in cooling mode refer to rated water flow rate, outlet water temperature of 7 °C and ambient temperature of 35 °C.

2. Heating capacity and electrical power consumption in heating mode refer to rated water flow rate, water outlet temperature of 45 °C and ambient temperature of 7 °CDB.

Dimensions

MCU050YHT

MyCond Diagram showing dimensions of propane MCU-YHP expansion modules.