Designer floor-standing fan coil units, Silent series

This is the perfect model that combines elegance, clean shapes and thinness so it makes perfectly integrable in blind spots as well in a renovation projects
Cooling capacity: 0.75 ... 3.1 kW
Heating capacity: 0.99 ... 6.3 kW
Designer floor-standing fan coil units, Silent series

Cooling, heating dehumidification and cleaning with one unit only. An ultra-slim fan coil with BLDC motor technology, it modulates the fan speed according to the user's needs. This type of fan provides low noise with high airflow compared to a conventional fan motor. 
The ultra-slim design with BLDC motor makes it the best choice for use in bedrooms. Thanks to the BLDC technology, the fan speed is infinitely adjustable to meet the needs of the user.

Silent series

  1. This model is designed for low temperature heating.
  2. Filters are easily removed from the housing, which makes them easy to clean during maintenance.
  3. Compact dimensions allow you to place the fan coil in any place without compromising the space of the room.
  4. The fan coil unit can be controlled using a buil-in touch-control panel with LED-display or via Wi-Fi.

Key advantages:

  • Ultra-slim body (only 134mm deep)
  • Artwork design
  • Low noise level
  • Wall-mounted installation
  • Touch-control panel with a LED display
  • Integrated 3-way valve
  • BLDC motor


smiling girl

Specifications Units MCFS-075T2
Silent
MCFS-150T2
Silent
MCFS-220T2
Silent
MCFS-300T2
Silent
Total cooling capacity1 kW 0,75 1,5 2,2 3,1
Heating capacity2 kW 0,99 2 2,8 4,2
Heating capacity3 kW 1,55 3,1 4,6 6,3
Connection diameter inch G1/2 G1/2 G1/2 G1/2
Maximum air flow rate m3/h 160 320 460 580
Minimum air flow rate m3/h 50 150 200 300
Maximum operating current A 0,12 0,16 0,21 0,24
Power input W 14 23 37 33
Maximum noise level4 dB(A) 39 40 42 42,1
Minimum noise level4 dB(A) 19,8 18,3 19,1 21
Net weight kg 16 22 28 34

The specifications refer to the following conditions:
1 – Cooling: inlet/outlet water temperature +7/+12 °C; indoor temperature +27/+19 °C
2 – Heating: inlet water temperature +50 °С, with water flow rate corresponding to the cooling mode; indoor temperature +20 °C
3 – Heating: inlet/outlet water temperature +70/60 °C; indoor temperature +20 °C
4 – Noise level means sound pressure level as per EN 12102:2008 and ISO 3745:2012

Dimensions

Model Units L
MCFS - 075T2 mm 694 588 134
MCFS - 150T2 mm 894 588 134
MCFS - 220T2 mm 1094 588 134
MCFS - 300T2 mm 1294 588 134

Dimensions

* Available as an option